IEEE 33 节点配电系统

图2 IEEE33节点配电系统接线图

支路数123456710111213141516171819节点i节点j123456710111213141516172192345671011121314151617181920支路阻抗0.0922+j0.0470.4930+j0.25110.3660+j0.180.3811+j0.19410.8190+j0.70700.1872+j0.61880.7114+j0.23511.0300+j0.74001.0440+j0.74000.1966+j0.06500.3744+j0.12381.4680+j1.15500.16+j0.71290.5910+j0.52600.7463+j0.501.20+j1.72100.3720+j0.57400.10+j0.15651.5042+j1.35节点j负荷100+j6090+j40120+j8060+j3060+j20200+j100200+j10060+j2060+j2045+j3060+j3560+j35120+j8060+j1060+j2060+j2090+j4090+j4090+j40支路数202122232425262728293031323334353637节点i节点j20213232462627282930313278111724212223242526272829303132332014213228支路阻抗0.4095+j0.47840.70+j0.93730.4512+j0.30830.80+j0.70910.60+j0.70110.2030+j0.10340.2842+j0.14471.0590+j0.93370.8042+j0.70060.5075+j0.25850.9744+j0.96300.3105+j0.36190.3410+j0.53622+j22+j22+j20.5+j0.50.5+j0.5联络开关本网中有32条支路、5条联络开关支路、1个电源网络,首端基准电压12.66kV、三相功率准值取10MVA、网络总负荷5084.26+j27.32kVA节点j负荷90+j4090+j4090+j50420+j200420+j20060+j2560+j2560+j20120+j70200+j600150+j70210+j10060+j40、