Electric Power System Equipment运行与维护
Operation And Maintenance2019年第24期
2019 No.24
10 kV配电线路常见故障原因及预防措施
陈君建
(广东电网有限责任公司汕尾陆丰供电局,广东汕尾 516600)
[摘 要]随着人民生活水平逐渐提高、国家经济不断发展,我国各行各业的用电量大幅度增加。当电力线路的改造及运维跟不上时代发展的需要时,线路出现的重过载、故障等情况有可能造成电力企业经济各方面的损失甚至危害人民群众的生命财产。文中简要分析了10 kV配电线路常见故障原因及预防措施。[关键词]10 kV配电线路;故障原因;预防措施[中图分类号]TM75 [文献标志码]A [文章编号]1001–523X(2019)24–0073–02
Analysis on Common Failure Causes and Preventive
Measures of 10 kV Distribution Lines
Chen Jun-jian
[Abstract]With the gradual improvement of people’s living standards and the continuous development of the national economy, the electricity consumption of all walks of life in China has increased significantly. When the transformation and operation and maintenance of the power line cannot keep up with the needs of the development of the times, the heavy overload and faults that occur in the line may cause losses in all aspects of the economy of the power enterprise and endanger the lives and property of the people. This requires us to treat it seriously. . Nowadays, building a safe, reliable, green and efficient smart grid has become a vision to lead the development of power grid enterprises. Therefore, this article will briefly analyze the common causes and preventive measures of 10 kV distribution lines.
[Keywords]10 kV distribution line;cause of failure;preventive measures当前我国工业生产、居民生活等用电大都是通过10 kV电压等级的配电线路进行输送,但10 kV配电线路在建设及日常运行维护中面临着诸多问题,如使用的设备数量多、受天气影响大等原因导致线路设备故障情况时常发生。为提高用电安全性、稳定性及可靠性,需要分析了解故障原因,及时做好预防措施。1 10 kV配电线路常见的故障原因
1.1 自然灾害因素
而产生大的电流迸发,承受不住的还会发生爆炸的情况,导
致线路短路故障,对线路产生非常大的破坏。
1.2.2 线路连接器装置不符合规定
10 kV配电线路大多为架空线路,架设于露天环境中,较
容易受到外界环境的影响,比如雷暴雨、台风等天气,在这样的极端恶劣天气下容易导致线路故障。雷暴雨天气导致线路产生大气过电压,造成绝缘子等电器设备绝缘击穿,从而引起线路接地或相间短路故障;台风天气带来的大风、大雨形成外力破坏,导致线路倒杆、断线或漂浮物挂在导线上等情况,引起线路故障跳闸。
1.2 10 kV配电线路自身设备存在缺陷
目前在我国很多地区都经常使用并沟线来进行线路导线
的连接,也是作为10 kV线路主要的一种连接器。在进行连接的时候有的还不是规整地放到线路连接器上而是选择缠绕的方式进行连接,当缠绕的十分混乱的时候,非常容易造成接触不良的现象,就会造成很大的危害,在经受不住极端天气的冲击而产生短路然后就会烧毁线路。
1.2.3 线路防雷的措施不足
因受地区经济发展及地形地势等因素的影响,部分电力
线路在布点架设时线路跨度大、线路分支多,导致电力线路供电半径长、线路网络复杂多样,线路设备繁多。有些电力设备安装的时间以及地点或存在差异,设备本身的质量也是各有不相同,有的设备质量比较好,有的设备质量就不是非常到位。因为设备批次的不同,不容易进行设备的管理以及检修检测工作。
因为设备年久失修,许多老旧的设备里面存在绝缘性能差的问题,当在电流通过的时候或者大规模使用电力时候,电力设备以及电力线路承受不住非常大的电流通过,所以就会产生短路甚至会被猛烈的电流击穿,从而导致跳闸甚至是烧毁。
1.2.1 配电线路绝缘子
虽然10 kV的线路在我国的应用是非常广泛的,但是对于
一些预防故障的措施做得还是很不到位,比如在比较严峻的户外环境里面,对防雷的措施做的不到位,尤其是对于那些季风带的地区,天气情况非常不稳定,没有安装合适的避雷器,所以当有雷雨天气的时候就会有因为雷电而发生事故,发生短路的情况。在安装避雷器的时候也会因为安装使用的位置不合格而达不到避雷的效果,当安装位置不符合要求时,有可能会因泄流的能力不好,雷电电流不能快速地消散,无法达到避雷的理想效果,从而产生严重的后果。
1.3 外力破坏造成10 kV配电线路发生故障
外力破坏在10 kV配电线路的日常运行事故原因中占了较大的原因,如机动车违反交通规则将立在公路旁的杆塔撞倒或撞断,导致架空线路断线或短路故障;市政工程施工,挖掘机等机械施工前没有认真核对地线电力电缆走向或不注意架空线路的情况下进行野蛮施工,挖断地下电力电缆或机械臂触碰到架空裸导线等情况造成严重的线路故障,给10 kV配电线路运行安全带来较大威胁。
2 10 kV配电线路常见故障的预防措施
2.1 受自然灾害因素影响的预防措施
绝缘子是10 kV线路上的主要物质,多数绝缘子长期暴露
在户外环境里面,在一些重污染地区,绝缘子表面容易积累很多污秽。设备运维单位如没有及时清理,在使用过程中可能会出现接触不良、闪络放电的现象。如受到雷击就会很容易产生连电的情况,会造成电流与电流之间的碰撞冲击,从在自然环境之中,风雨雷电等自然现象在目前是人类无法控制的,因此我们只能尽力地将预防做到最好,减少对人们的影响。比如雷击自然灾害,我们可以在10 kV配电线路中安装优质的避雷装置,在放置之前测量好适当的位置,并进行实验测量仪来证明是否可以达到避雷的效果,特别在易受
2019.24 电力系统装备丨73
2019年第24期
2019 No.24
运行与维护
Operation And Maintenance电力系统装备
Electric Power System Equipment电厂提高脱硫电气系统可靠性的优化策略探讨
崔 智
(广东红海湾发电有限公司,广东汕尾 516600)
[摘 要]随着我国经济实力的增强,民众的物质生活与精神生活开始变得丰富,用电需要持续增长时也开始关注环保问题,电气系统可靠性在脱硫工程中的运用是新时期电厂节能环保方面的关键举措。基于此,本文对电气系统可靠性进行解析与探寻,希望为电厂脱硫项目提供既定的参考依据。[关键词]脱硫;电气系统;可靠性;优化;策略[中图分类号]TM76 [文献标志码]A [文章编号]1001–523X(2019)24–0074–02
Discussion on Optimization Strategy for Improving Reliability of
Desulfurization Electrical System in Power Plants
Cui Zhi
[Abstract]With the enhancement of China’s economic strength, people’s material and spiritual life has become richer. When electricity demand needs to continue to grow, it has begun to pay attention to the issue of condemnation. The use of electrical system reliability in desulfurization projects is the energy conservation and environmental protection aspect of power plants in the new era. Key initiatives. In view of this, the author analyzes and explores the reliability of electrical systems, and hopes to provide an established reference for power plant desulfurization projects.
[Keywords]desulfurization; electrical system; reliability; optimization; strategy电气可靠性在脱硫项目中被多次提及,其运用既可以化解机电一体化管控方面的困局,又可以提高电气可靠性,并且调整脱硫项目,对提高脱硫效率与实现电厂的稳步发展有着极为重大的价值。1 改造前的问题以及预期改造效果
1.1 脱硫电气系统改造前存在的问题
(1)原脱硫6 kV系统使用的单母线双电源接线模式并不是最佳选择。尽管双电源间有快切设备,然而因为已取缔旁路设备,假如转换回路与快切设备形成故障,只要故障排除
不成功,脱硫系统会全部失电,导致机组停止运转。
(2)单母线接线模式无助于载荷的均衡配置。从过往的运转状况来说,因为脱硫系统载荷很大,高压厂的变压设备带脱硫设备运转的6 kV旁支(B1段)通常会满负荷运转,无助于高压设备的平稳运转。原脱硫400 V系统预设1段作业段与1段公用段,两部机组间的创设可靠性下降,无法完成载荷的科学配置,任意一段400 V母线停止供应电能,都能导致脱硫系统停止运转。
(3)原脱硫系统部分载荷由单电源供应电能,并未预设
雷击的地点放置更多更好的避雷装置。对线路里面的绝缘子物质要进行及时地检查,使其在过大电流通过的时候可以做到绝缘的作用,不会轻易地受到雷击的影响。对于台风天气,应在线路的建设过程中根据地区的防风标准,加强杆塔基础建设,提高防风能力;在已投运多年的配电线路上,应进行防风加固,如档距较大线段增设杆塔或增加拉力线等措施以增加防风能力,从而减少特殊天气对线路的伤害。
2.2 配电线路自身装置存在故障的预防措施
我们在选择设备的安装的时,需要选择批次相同质量优良的电力设备,因为在电力线路里面设备是帮助运输电流的最重要的硬件,在采购设备的时候一定要认真比较,选择质量优质的电力设备,这样才能使线路的使用时间更加长久,线路运行更加稳定。对于那些已经比较老旧的设备,需要指派专业的技术人员进行定期的维护检测,增长设备的使用寿命。当发现有的设备已经存在安全隐患的时候我们应及时进行检修更换,防患于未然。
2.3 遭受外力破坏的预防措施
提醒施工人员注意,减少挖掘机施工挖掘破坏地下电力电缆。
另外对于架设在道路两旁的杆塔,需完善安健环反光标志,设置防撞墩,增强现场的监督以及监视,增强人们保护电力系统的意识。3 结束语
综上所述,随着我国综合国力的不断增强,现代化进程不断加快,电力系统的发展也越来越快,需要不断加强电力系统的建设工作,通过对10 kV配电线路故障原因的分析,提出针对性的预防措施,从而有效地规避风险,提高10 kV配电线路的安全性、稳定性、可靠性,不断满足人们的生活需求。
参考文献
[1] 李冬冬.10 kV农村配电线路故障处置与防范研究[D].山东:山东大学,2016.[2] 于闯.沈阳地区10 kV配电线路防雷措施研究[D].北京:华北电力大学,2018.[3] 陈亚飞.德庆地区10 kV电压等级避雷器故障分析及对策[D].长春:吉林大学,2017.[4] 马海龙.10 kV配电线路故障与其自动化运行维护[J].自动化应用,2018(08):120-121.[5] 赵立峰.10 kV配电线路常见故障及运行维护对策探析[J].机电信息,2013(21):30-31.
根据市政建设需要及线路管理维护的需要,新建设或改
造的配电线路大都沿着道路设计安装建设。为减少外力破坏,需尽可能将线路改为绝缘程度较高的绝缘架空线路或电缆,减少施工机械触碰裸导线;完善标示,让人们知道地下是电力电缆,加强施工地段的巡视,派发安全隐患通知书,从而
74丨电力系统装备 2019.24
因篇幅问题不能全部显示,请点此查看更多更全内容